The average temperature at Dyna-Tech’s headquarters (Branchburg NJ) on Christmas Eve was just under a brisk 10°F, which is caliber of cold that’ll keep your cooling tower basin heaters humming. But how can you be confident that your basin heaters are running as safely and efficiently as possible? It a great question that deserves a great answer: Marley’s Advanced Basin Heater System.

With upgraded components for circuit protection, personal safety, setpoint adjustability, optional temperature feedback, digital control interface and push-button testing, Marley’s Advanced Basin Heater (ABH) Control Panel is the solution you’ve been looking for. This system provides owners with the control, real-time monitoring and flexibility that basic basin heater systems have been lacking – until now.

Key benefits of the ABH System:

  • Solid-state digital controller with LCD display shows temperature set point and real-time basin water temperature and allows operator to adjust set points manually from the door of the enclosure or remotely from a BMS.
  • Adjustable setpoints via digital controller enable automatic control between system shutdowns and waterside economizing applications
  • Optional 4-20mA basin temperature feedback module for remote monitoring at BMS
  • NEMA 4X fiberglass outdoor enclosure
  • Lockable disconnect on all panels
  • A thermal magnetic circuit breaker disconnect is standard – providing electrical protection for the control panel and power wiring.
  • The heater element push-to-test circuit provides the operator with an easy means to test heater functionality during summer months in preparation for cold weather.
  • Marley PT-100 temperature RTD is industrial-rated, providing accurate measurements with the ability to extend wiring long distances.
  • Built-in low water cutout circuit ensures the high-density heater element is covered with water before being energized, protecting the heater from burn-out.
  • Output status contacts for BMS communication module determines contactor closure and heater element functionality.
  • Industrial-hardened components are dependable and reduce field callbacks.

Marley’s ABH control panel can also be integrated into other systems, including the Marley AIO (All-in-One) Control Panel, CAN-DO motor starter panel and SPPC control panel. It is also adaptable to various process applications, including plate-and-frame heat exchangers, remote storage tanks and cooling loop pre-heaters.

Marley’s ABH control panel can also be integrated into other systems, including the Marley AIO (All-in-One) Control Panel, CAN-DO motor starter panel and SPPC control panel. It is also adaptable to various process applications, including plate-and-frame heat exchangers, remote storage tanks and cooling loop pre-heaters.

Click on the attached video from SPX’s Electrical Products Manager, Mark Groothuis, to learn more:

(101) Marley® Advanced Basin Heater Control Panel – YouTube

Do you need cooling tower parts, service, or inspections? Are you considering refurbishing your cooling system or replacing it all together – or maybe you just want to talk to someone about advancements in cooling technology, system efficiency and current industry standards?

If so, give us a call at 908-541-1010 or click the (contact us) button at the bottom of the page.  Our sales engineers are ready to answer your questions and discuss your needs.